SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 70 of 103

TÜV Certified

Configuration

Conditions

Triguard Interface,

8161

Simplex

(2003 implemented in

a set of three

modules)

Certified as safety related and can be used for
safety-critical applications in SIL 3.

Local Chassis
Interface,

MBB

Simplex

(2003 implemented in

a set of three

modules)

Certified as safety related and can be used for

safety-critical applications in SIL 3.

Remote Slave
Interface,

MRB01XS

Simplex

(2003 implemented in

a set of three

modules)

Certified as safety related and can be used for
safety-critical applications in SIL 3.

Remote Master
Interface

MRB04XM

Simplex

(2003 implemented in

a set of three

modules)

Certified as safety related and can be used for
safety-critical applications in SIL 3.

Table 13 - Central Modules

TÜV Certified

Configuration

Conditions

Digital Inputs

MDI32BIS, TMR,

24VDC

MDI32GIS, TMR,

48VDC

MDI32FIS, TMR,

120VDC

Internal 2oo3

(2oo3 implemented in

a single module)

Normally energized (de-energize to trip): certified
SIL 3.

Normally de-energized (energize to trip): certified
only for applications that fulfil the requirements
under section 3.2.4.

Digital Inputs

MDI64BNS,

Simplex, 24VDC

Simplex 1oo1

Normally energized (de-energize to trip).

Certified as non-interfering and can be used for
non-safety-critical input devices.

Analogue Inputs

MAI32(L/M)AD, TMR

0-5/10V

MAI32(N/P)AD, TMR

0-20/40mA

Internal 2oo3

(2oo3 implemented in

a single module)

Within the manufactures specified safety accuracy
limits. The safety state of the analogue input has to
be defined to 0 mA/0 V

Certified SIL 3.

Table 14- Input Module, Triguard I/O