SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 59 of 103

4.2.4 High Density Module Configuration Checklist

Description

Reference

For each of the I/O signal types, do the I/O

module settings provide the correct

characteristics and behaviour for the intended

sensor or actuator?

3.7.1

Have the thresholds been verified with both

increasing and decreasing field signal levels

and with margins to allow for the accuracy and

calibration to ensure that they do not result in

overlapping bands?

3.7.1

Is consistent use made of front panel

indicators?

Ensure that “green” is not used for abnormal

conditions.

3.7.1

Have the update rates been set such that they

are acceptable for fault annunciation

requirements and that the rates result in the

system’s response within the PST

E

.

3.7.1

Have the settings been defined according to a

field device type setting, and minimal use has

been made of channel specific settings?

3.7.1

For any non-standard configuration settings,

have tests been defined and executed to 100%

test the required operation?

3.7.1

4.2.5 Processor and Other Configuration

Description

Reference

If Peer-to-Peer communications is used, are the

timeouts set to ensure a response time less

than that required by PST

E

?

3.10

Has the diagnostic access password been set?

3.6.2

Password:

Has the security has been set up on the IEC1131

TOOLSET

?

3.11.1

Engineering supervisor password

Engineer/ Application programmer password

Maintenance engineer password

General user password