Rockwell Automation T8094 8000 Series TMR System Safety Manual User Manual

Page 92

Advertising
background image

SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 71 of 103

TÜV Certified

Configuration

Conditions

Digital Outputs

MDO32BNS, TMR,

24 VDC

MDO16GNS, TMR,

48VDC

MDO16FNS, TMR,

120VDC

MDO16CNS, TMR,

120VAC

Internal 2oo3

(2oo3 implemented in

a single module)

Normally energized (de-energize to trip): certified
SIL 3.

Normally de-energized (energize to trip): certified
only for applications that fulfil the requirements
under section 3.2.4.

May be used in single module or active/standby
configurations.

Analogue Output

MAO04NND, TMR,

0-22mA

Not safety related but

interference free

Certified as non-interfering and can be used for non-
safety-critical devices.

Table 15- Output Modules, Triguard I/O

TÜV Certified

Configuration

Conditions

Analogue Output /
Pulse Input

MHB44IND, TMR,

4-20mA,

1Hz-35KHz

Not safety related but

interference free

Certified as non-interfering and can be used for non-
safety-critical devices.

Table 16 – Triguard Multi-purpose Modules

Conditions

Controller Chassis

8100

Certified as safety related and can be used for safety critical
applications in SIL 3.

Primary,

Secondary

and

Remote Triguard Chassis

Certified as safety related and can be used for safety critical

applications in SIL 3.

Power Supplies

PAC, PDC

Certified as safety related and can be used for safety critical
applications in SIL 3.

Table 17 – Auxiliary Chassis and PSUs

Advertising