4.2.6 Testing

Description

Reference

Have all of the functions used been fully tested?

3.11.2

and

3.11.3

Has the program been fully tested? The code

checker can be used to highlight which

programs have changed during modification -

see para. 3.9.12.2.

3.11.6

Record the application scan time (read from the

Toolset display)

Record the system throughput time (output SOE

– input SOE)

Record the system throughput time where

Peer-to-Peer communications is required

(output SOE – input SOE)

Are the scan and response times in accordance

with the PSTE requirements (< ½ PST

E

)?

Have the climatic conditions been verified to be

suitable?

3.13