4.2.6 Testing
Description
Reference
Have all of the functions used been fully tested?
3.11.2
and
3.11.3
Has the program been fully tested? The code
checker can be used to highlight which
programs have changed during modification -
see para. 3.9.12.2.
3.11.6
Record the application scan time (read from the
Toolset display)
Record the system throughput time (output SOE
– input SOE)
Record the system throughput time where
Peer-to-Peer communications is required
(output SOE – input SOE)
Are the scan and response times in accordance
with the PSTE requirements (< ½ PST
E
)?
Have the climatic conditions been verified to be
suitable?
3.13