Rockwell Automation T8094 8000 Series TMR System Safety Manual User Manual

Page 87

Advertising
background image

SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 66 of 103

TÜV Certified

Configuration

Conditions

Guarded Digital

Outputs

T7461A, 24 VDC

T7485 L/H, 120 VAC

Fail-safe single

module (1oo1)

or

Fault tolerant dual

modules (2oo2)

Normally energized (de-energize to trip): certified.
Normally de-energized (energize to trip): certified
only for applications that fulfil the requirements

under section 3.2.4, and only if the outputs are
dynamically transitioned 0→1→0 or 1→0→1 at a

period not greater than the second fault occurrence
time.

Monitored Guarded

Outputs

T7481, 24 VDC

T7484, 110 VAC

T7488, 120 VDC

Fail-safe single

module (1oo1)

or

Fault tolerant dual

modules (2oo2)

Normally energized (de-energize to trip): certified.
Normally de-energized (energize to trip): certified

only for applications that fulfil the requirements
under section 3.2.4.

Other Outputs

T7441A, 24 VDC

T7444, 110 VAC

T7446L/H, relay

T7454, 110 VAC,

isolated

T7464, 110 VAC,

guarded

T7470A, Analog

T7480A, Analog,

guarded

Not safety related but

interference free

Certified as non-interfering and can be used for
non-safety-critical output devices.

Input and Output

Multiplexer

T7491

Not safety related but

interference free

Certified as non-interfering and can be used for
non-safety-critical output devices.

Table 12 - Output Modules, Low Density I/O

Advertising