SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 40 of 103

3.11.1 IEC1131 Workbench Configuration

The IEC1131 workbench supports 16 levels of password access, level 0 being the
highest access level. Each workbench function (for example, viewing, editing,
compiling, downloading) may be identified for use only by users with an access level
above a certain level.

User access passwords shall be implemented, the recommended access levels
are:

0 – Engineering supervisor

2 – Engineer/Application Programmer

4 – Maintenance Engineer

8 – General User

With the functions allocated as shown in Table 7.

Function

Min.

access

level

Function

Min.

access

level

Global Protection

8

Debug application

8

Overwrite with archive

2

Simulate application

8

Backup on archive

8

Download/stop/start application

4

Project Description

4

Update application

4

History of modifications

8

Communications parameters

8

I/O Connection

2

Set cycle time

2

Global Variables

2

Set execution mode

2

Global & Common Defined Words

2

Change variable state

4

Create New

2

Lock/Unlock variable

4

Move program in hierarchy

2

Control SFC

4

Verify

8

Control Timer

4

Make application code

4

Set IL Breakpoint

4

Touch application

4

Set SFC Breakpoint

4

Conversion tables

2

Create graphics

8

Application runtime parameters

2

List of variables

8

Compiler options

2

List of time diagrams

8

Resource definition

2

Print project document

8

Customise project document

4

Table 7 - IEC1131 Workbench Recommended Access Levels