Rockwell Automation T8094 8000 Series TMR System Safety Manual User Manual
Page 61

SAFETY MANUAL
D oc N umber T8094
I ssue 27 – June 2013
Page 40 of 103
3.11.1 IEC1131 Workbench Configuration
The IEC1131 workbench supports 16 levels of password access, level 0 being the
highest access level. Each workbench function (for example, viewing, editing,
compiling, downloading) may be identified for use only by users with an access level
above a certain level.
User access passwords shall be implemented, the recommended access levels
are:
0 – Engineering supervisor
2 – Engineer/Application Programmer
4 – Maintenance Engineer
8 – General User
With the functions allocated as shown in Table 7.
Function
Min.
access
level
Function
Min.
access
level
Global Protection
8
Debug application
8
Overwrite with archive
2
Simulate application
8
Backup on archive
8
Download/stop/start application
4
Project Description
4
Update application
4
History of modifications
8
Communications parameters
8
I/O Connection
2
Set cycle time
2
Global Variables
2
Set execution mode
2
Global & Common Defined Words
2
Change variable state
4
Create New
2
Lock/Unlock variable
4
Move program in hierarchy
2
Control SFC
4
Verify
8
Control Timer
4
Make application code
4
Set IL Breakpoint
4
Touch application
4
Set SFC Breakpoint
4
Conversion tables
2
Create graphics
8
Application runtime parameters
2
List of variables
8
Compiler options
2
List of time diagrams
8
Resource definition
2
Print project document
8
Customise project document
4
Table 7 - IEC1131 Workbench Recommended Access Levels