SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 95 of 103

Direction:

From ITSTM to each DIPT

Values:

not specified

9.10.6.7 DOM, digital output mode

Purpose:

The DOM (digital output mode) is an encoded output from the OTSTM to each
RMET. It is not for direct use by the user application.

Data type:

analogue

Direction:

From OTSTM to each RMET

Values:

not specified

9.10.6.8 FLTA / FLTB, fault A / B

Purpose:

The FLT (fault) outputs let the DIPT and RMET tell the application when there
is a fault on slice A or slice B of a duplex input (DIPT) or output (RMET)
channel

Data type:

Boolean

Direction:

From ITSTM to user application
From OTSTM to user application

Values:

TRUE – there is a fault on the applicable slice
Otherwise FALSE

Notes:

The FLT outputs from the DIPT are latched until a reset command is received
from the related ITSTM.

9.10.6.9 FRQ, frequency

Purpose:

The FRQ (frequency) input sets the quantity of times the ITSTM or OTSTM will
start its test sequences in a time of 24 hours.

Data type:

analogue

Direction:

From application to ITSTM or OTSTM

Values:

1, 2, 3 or 4

Notes:

A value less that 1 is treated as 1, and a value larger than 4 is treated as 4.

9.10.6.10 HR, hour

Purpose:

The HR (hour) parameter is used by the ITSTM and OTSTM to control their
scheduled testing.

Data type:

analogue

Direction:

From controller RTC to ITSTM and OTSTM

Values:

0 to 23

Notes:

The HR input is usually connected to the TrustedTM controller's real time clock.

9.10.6.11 IP, process input

Purpose:

The IP (process input) parameter carries the value from a PI-732 analogue
input channel as a raw unscaled integer

Data type:

analogue

Direction:

From application to LFLT

Values:

0 to 65,535

9.10.6.12 IPA / IPB, input A / B

Purpose:

The IPA and IPB parameters carry the measured input for the channel for their
slices.

Data type:

Boolean

Direction:

From application to DIPT

Values:

TRUE – input channel high
FALSE – input channel low

Notes:

For a simplex input module, connect IPB to the same point as IPA.