SAFETY MANUAL

D oc N umber T8094
I ssue 27 – June 2013

Page 57 of 103

Description

Reference

Has the allocation of signals to I/O modules

and channels considered each of the signals’

function?

Ensure that potential module and power group

failures result in either continued safety

function or fail-safe operation.

3.2.1

Do safety related inputs and outputs use only

those configurations identified as safety

related

3.2.1

Are there any safety-related, normally de-

energised outputs?

If so have redundant power sources, power

failure warning and line monitoring been

provided?

3.2.4

Have sensor fault conditions been taken into

account?

3.3

Have actuator fault conditions been taken into

account?

3.4

Have field power supplies conforming to

EN6101-1 or EN 60950 been used?

3.13.4

4.2.2 Language Selection Checklist

Description

Reference

Has application programming for safety-related

sections been limited to the FB programming

language?

3.11.2

Are any functions not in the previously tested

libraries required? If so has provision been

made to adequately test these functions?

3.11.3

Ensure that the programming languages

classified as non-safety (‘C’ and SFC) are NOT

used for safety-related projects

3.11.2