95
COS Message Format
The XM-123 COS message contains six bytes of data as defined in the table
below. The COS data can also be requested explicitly through Assembly
Object (Class ID 0x4), Instance 100 (0x64), Data Attribute (3).
XM Status Values
The following tables describe the XM Status values that are included in the
COS messages.
XM-123 COS Message Format
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Relay 1
Status
Setpoint
Multiplier
Status
Alarm 2 Status
Alarm 1 Status
1
Relay 2
Status
Reserved
Alarm 4 Status
Alarm 3 Status
2
Relay 3
Status
Reserved
Alarm 6 Status
Alarm 5 Status
3
Relay 4
Status
Reserved
Alarm 8 Status
Alarm 7 Status
4
Relay 5
Status
Reserved
Alarm 10 Status
Alarm 9 Status
5
Reserved
Reserved
Alarm 12 Status
Alarm 11 Status
Alarm Status Descriptions
Alarm Status Value
Description
0
Normal
1
Alert
2
Danger
3
Disarm
4
Transducer Fault (Sensor OOR)
5
Module Fault
6
Tachometer Fault
7
Reserved
Setpoint Multiplier Status Descriptions
Setpoint Multiplier Status Value Description
0
Not Activated
1
Activated