135
Instance Attributes
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Table C.44 Speed Measurement Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Speed Value
REAL
The measured speed
value.
CPM
4
Get
Status
BOOL
Indicates if a fault or
alarm has occurred.
0 = Operating without alarms or
faults.
1 = Alarm or fault condition
exists. The Speed Value
attribute may not represent the
actual field value.
5
Get
Maximum
Speed
REAL
The maximum (peak)
measured speed value
(positive or negative)
since the most recent
reset.
CPM
12
Get/Set
Time Constant
UINT
The time constant value
used for exponential
averaging of the Speed
Value (a low pass
filter/output smoothing
filter).
Milliseconds
Table C.45 Speed Measurement Object Services
Service
Code
Class/Instance Usage
Name
Description
05
h
Instance
Reset
Clears Maximum (Peak)
speed to 0.
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
1