Determines whether the relay is failsafe or
non-failsafe.

Failsafe operation means that when in alarm, the
relay contacts are in their "normal," de-energized, or
"shelf-state" positions. In other words, normally
closed relays are closed in alarm, and normally open
relays are open in alarm. With failsafe operation, a
power failure equals an alarm.

The following are true of a relay in failsafe
operation:

•

The relay is energized when power is applied to
the module.

•

The relay in a nonalarmed condition has power
applied to the coil.

•

In alarm condition, power is removed from the
relay coil, causing the relay to change state.

For non-failsafe operation, the following are true:

•

Under nonalarm conditions, the relay closes the
circuit between the common and the N.C.
(normally closed) terminals.

•

Under alarm conditions, the relay changes state to
close the circuit between the common and the
N.O. (normally open) terminals.

For failsafe operation, the following are true:

•

Under nonalarm (with power applied to the unit)
conditions, the relay closes the circuit between the
common and the N.O. terminals.

•

Under alarm or loss-of-power conditions, the relay
changes state to close the circuit between the
common and the N.C. terminals.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Failsafe Relay

Failsafe
Option

XM Configuration
Utility

EDS File

Check means
failsafe

Failsafe

Clear means
non-failsafe

Nonfailsafe