Xm-123 full scale tables – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 152

Publication GMSI10-UM003D-EN-P - May 2010
144
XM-123 Full Scale Tables
Use the following tables to help you determine the optimal Full Scale value for
the XM-123 module. Refer to the table that corresponds to the units of
vibration that will be used for monitoring.
Table D.1 XM-123 Measuring Acceleration with Accelerometer (100 mV/g)
Max Vibration Level
Full Scale Setting
g’s peak
1Hz HPF
5Hz HPF
10Hz HPF
40Hz HPF
1000Hz HPF
1
0.1
5
0.75
10
1
30
3
40
4
50
5
Table D.2 XM-123 Measuring Velocity with Accelerometer (100 mV/g)
Max Vibration Level
Full Scale Setting
Max High Frequency Peak Amplitude
ips peak mm/s RMS
1Hz HPF
5Hz HPF
10Hz HPF
40Hz HPF
1000Hz HPF
(g pk)
0.3
10
N/A
0.005
0.01
0.03
0.75
4
1
40
N/A
4
3
100
0.009
0.018
0.072
4
10
360
0.085
0.17
0.67
12
30
1000
0.25
0.5
2.2
40
100
3600
0.83
1.66
6.66
120
Table D.3 XM-123 Measuring Velocity with Velocimeter (100 mV/ips)
Max Vibration Level
Full Scale Setting
ips peak
mm/s RMS
1Hz HPF
5Hz HPF
10Hz HPF
40Hz HPF
1000Hz HPF
3
100
0.75
10
360
1
20
700
2
30
1000
3
Table D.4 XM-123 Measuring Displacement with Velocimeter (100 mV/ips)
Max Vibration Level
Full Scale Setting
mils pp
micrometers pp
1Hz HPF
5Hz HPF
10Hz HPF
40Hz HPF
1000Hz HPF
5
125
N/A
0.05
0.1
0.35
N/A
10
250
0.1
0.2
0.7
50
1250
0.15
0.3
1.05