Manually resetting relays – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 56

Publication GMSI10-UM003D-EN-P - May 2010
48
The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.
Refer to Module Indicators on page 45 for more information about the LED
indicators.
Manually Resetting Relays
The XM-123 has an external reset switch located on top of the module, as
shown in Figure 2.34.
Figure 2.34 Reset Switch
The switch can be used to reset all latched relays in the module. This includes
the relays in the Expansion Relay Module when it is attached to the XM-123.
MS Indicator State
Description
Flashing Red and Green
Device self-test is in progress.
Solid Green or Flashing Green
Device self-test completed successfully,
and the firmware is valid and running.
Flashing Red
Device self-test completed, the hardware is
OK, but the firmware is invalid. Or, the
firmware download is in progress.
Solid Red
Unrecoverable fault, hardware failure, or
Boot Loader program may be corrupted.
IMPORTANT
The Reset switch resets the relays only if the input is no
longer in alarm or the condition that caused the alarm is no
longer present.
AERODERIVATIVE
1440-VAD02-01RA
Press the Reset
Switch to reset the
relays