Mounting the terminal base unit – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 21

Publication GMSI10-UM003D-EN-P - May 2010
13
Figure 2.6 Grounded DeviceNet V- at XM Module
For more information on the DeviceNet installation, refer to the ODVA
Planning and Installation Manual - DeviceNet Cable System, which is available
on the ODVA web site (http://www.odva.org).
Switch Input Grounding
The Switch Input circuits are functionally isolated from other circuits. It is
recommended that the Switch RTN signal be grounded at a single point.
Connect the Switch RTN signal to the XM terminal base (Chassis terminal) or
directly to the DIN rail, or ground the signal at the switch or other equipment
that is wired to the switch.
Mounting the Terminal
Base Unit
The XM family includes several different terminal base units to serve all of the
XM modules. The XM-940 terminal base, Cat. No. 1440-TB-A, is the only
terminal base unit used with the XM-123 module.
To
Ground
Bus
ATTENTION
Use of a separate DeviceNet power supply is not
permitted. See Application Technique "XM Power Supply
Solutions", publication ICM-AP005A-EN-E, for guidance
in using XM with other DeviceNet products.