Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 125

Publication GMSI10-UM003D-EN-P - May 2010
117
1
The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll connection is
already established with a master/scanner. Attempting to do so will result in an "Object State Conflict" error
(error code 0xC). These Parameter instances are a little more flexible than the actual Connection Object
attributes because they can be set while the connection is in the NON-EXISTENT state (before the
master/scanner allocates the connection).
27
No
Relay 4 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
2 = Alarm 3
3 = Alarm 4
4 = Alarm 5
5 = Alarm 6
6 = Alarm 7
7 = Alarm 8
8 = Alarm 9
9 = Alarm 10
10 = Alarm 11
11 = Alarm 12
0
28
No
Relay 5 Alarm Identifier B
USINT
0 = Alarm 1
1 = Alarm 2
2 = Alarm 3
3 = Alarm 4
4 = Alarm 5
5 = Alarm 6
6 = Alarm 7
7 = Alarm 8
8 = Alarm 9
9 = Alarm 10
10 = Alarm 11
11 = Alarm 12
0
29
No
Channel 1 Filter Type
USINT
0 = Tracking
1 = Bandpass
0
30
No
Channel 2 Filter Type
USINT
0 = Tracking
1 = Bandpass
0
31
No
Poll Connection Produced
Connection Path
1
USINT
101-102 (Assembly Object
instance number)
101
32
No
Poll Connection Produced
Connection Size
1
UINT
4-124
36
Table C.22 Parameter Object Instances
Instance
Read
Only
Name
Data Type
Valid Values
Default Value