Services, Alarm object (class id 31dh), Class attributes – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 128: Instances, Instance attributes, Class attributes instances instance attributes, Alarm object (class id 31d, Class attributes instances

Publication GMSI10-UM003D-EN-P - May 2010
120
Services
Alarm Object
(Class ID 31D
H
)
The Alarm Object models a two-stage (alert and danger levels) alarm.
Class Attributes
Instances
There are 12 instances of this object
Instance Attributes
Table C.26 Acknowledge Handler Object Services
Service
Code
Class/Instance Usage
Name
0E
h
Instance
Get_Attribute_Single
10
h
Instance
Set_Attribute_Single
Table C.27 Alarm Object Class Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
1
Get
Revision
USINT
Revision of the
implemented object.
2 (indicates that Threshold
Multiplier is a REAL instead of
USINT)
Table C.28 Alarm Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Alarm Status
3 BITS
The current status of the
alarm.
0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
4
Get/Set
Alarm Enable
BOOL
Indicates whether this
alarm object is enabled.
0 = Disabled
1 = Enabled