10

Guideline 11 - Operational altitude above sea level

may not exceed 3300 ft (1000 m). Derate horsepower

3% for each 1000 ft (300 m) above this altitude.

3.2 Mounting

- This Paragraph outlines the proceĆ

dures to be followed to mount the FlexPak Plus controlĆ

ler.
Determine the exact placement of the Chassis on the

Panel. (Refer to Figure 3.3 for mounting dimensions.)

Scribe the panel. Drill three holes large enough to acĆ

cept #10 mounting bolts. Scrape the paint around the

holes to allow washers and bolts to make a ground conĆ

tact.

3.3 Power Wiring

- This Paragraph briefly outlines

the procedures to be followed when wiring aĆc power supĆ

ply lines to the controller and dĆc control circuits to the

drive. A basic connection diagramis given at Figure 3.4.

DANGER

BEFORE WIRING, MAKE SURE THAT AĆC LINE

DISCONNECT SWITCH IS LOCKED OPEN.

EVEN IF POWER HAS NOT BEEN APPLIED TO

THE INCOMING LINE, THIS PRACTICE ASĆ

SURES PERSONAL SAFETY. IF NO LOCKOUT

DEVICE EXISTS, REMOVE THE FUSES WITH AN

INSULATED TOOL AND PLACE A WARNING

TAG ON THE BOX.

Figure3.3 - Mounting Dimensions