TABLE 5.A - TROUBLESHOOTING SUGGESTIONS FOR THE COMPLETE CONTROLLER

Symptom

Probable Cause

Recommended Procedures

1. POWER ON/OFF

circuit breaker

trips or fuses clear

when power is apĆ

plied.

Incorrect wiring conĆ

nections to controller;

from controller to moĆ

tor; in motor.

V Connect ohmmeter from terminal 38 to 39 on TB.

V Remove aĆc power at the disconnect.

V Remove leads to L1, L2, L3, A1, A2 and F1, F2, on incoming side of controller's

respective location.

V Open the power disconnect switch.

V Check for a ground condition at L1/181, L2/182, L3/183, A1, A2, F1 and F2. Do this at

controller (internal) side of 1TB. If a ground is discovered, check wiring connections

on Power Cube and motor field terminals F1 and F2.

V If no ground exists, examine the controller chassis for loose wires and/or foreign

objects.

V If no ground exists and if no foreign objects are discovered, reconnect the incoming

conductors A1, A2 and F1 and F2. Then check for grounds at these terminals.

V If a ground is found, it is in the conductors to the motor or in the motor itself.

V Disconnect the motor from the conductors at the drive motor.

V Test A1, A2, F1 and F2 conductors for a ground. (If one exists, examine connections

and insulation for areas where shorts could occur.)

V If no grounds are found in the conductors, check the motor for a ground condition. If

a ground is located here, examine and/or replace the motor, as necessary.

Short in Power Cube.

V Replace Power Cube.

Short in Field Supply.

V Replace Field Supply.

2. Drive motor does

not start.

Main aĆc line disconĆ

nect not closed; or

fuse blown; or no

power applied ahead

of disconnect.

V Check disconnect switch, fuses in it, and voltage on line.

Drive interlocks preĆ

venting operation. 32

to 33 on TB

V Verify that all userĆinstalled interlocks are in a state (physical condition and wiring

connections) to allow a start.

Drive motor thermoĆ

stat wires not conĆ

nected on FlexPak

Plus controller termiĆ

nals 34 and 132 on

TB.

V Check connections to thermostat: at drive motor P1, P2; at controller 34, 132.

V Check for open thermostat inside motor. Make a resistance check of thermostat. (It

should read a short, or low resistance, if it is closed,

External overload

wires not connected

on FlexPak Plus conĆ

troller terminals 34

and 33 on TB.

V Check connections to external overload. (Blower Motor Starter O/L)

V Check for open overload, Make a resistance check to overload. (It should read a

short, or low resistance, if it is closed.)

Drive thermostat wires

not connected on

FlexPak Plus controlĆ

ler terminals 132 to

232

V Check connections to thermostat at drive power bridge heat sink, at controller 132 or

232.

V Check for open thermostat. Make a resistance check to the thermostat. (It should

read a short, or low resistance, if it is closed.

3. In nonĆreversing

controllers only . .

. Controller's M

contactor not

picking up when

START switch is

Faulty M contactor.

V Open the power disconnect switch,

V Examine M contactor for firm seating.

V On the M contactor, connect an ohmmeter on 139 and 39 Wires, The reading should

be 150 to 1000 ohms

V If these readings cannot be obtained, replace the M contactor. (Refer to Table 6.A.)

START switch is

pressed (closed).

Faulty start/Stop

switch.

V Check START/STOPswitch, but first remove aĆc line power at main disconnect.

V Connect ohmmeter to terminal 32 on the Remote Operator Adapter.

V Touch probe to terminal 38 on the Remote Operator Adapter.

V Place switch in the START (closed) position,

V If the switch is property functioning, a short will be seen on the meter.

V Check the STOPfunction. Place the RUN/JOG switch in the RUN position. Connect

the ohmmeter to terminals 32 and 35, Place the switch in the STOP position, which

should open it if it is functioning correctly. If there is a short, it will be seen on the

meter. If there is no short, the circuit is opened, and the switch is functioning correctly.

V Using similar techniques, test the RUN/JOG switch in the RUN position at terminals 32

and 35. When the switch is in the RUN position, a short should be read.

DANGER

IF CIRCUIT BREAKER HAS TRIPPED OR FUSES HAVE CLEARED,THE

FIELD SUPPLY AND ITS WIRING MUST BE INSPECTED FOR DAMAGE.

AFTER REĆAPPLYING POWER TO THE DRIVE, THE FIELD VOLTAGE

MUST BE REĆCHECKED FOR PROPER VOLTAGE AT MOTOR TERMIĆ

NALS F1, F2. IF THIS VOLTAGE IS BELOW 90% OF THE FIELD VOLTAGE

SPECIFIED ON THE MOTOR NAMEPLATE, THE DRIVE MUST NOT BE

STARTED UNTIL PROPER VOLTAGE IS OBTAINED. FAILURE TO

FOLLOW THIS PROCEDURE COULD RESULT IN OVERSPEEDING THE

MOTOR AND/OR THE MACHINERY COUPLED TO THE MOTOR SHAFT

AND POSSIBLE FATAL INJURY.