DANGER

15>

A.)

AN EXTERNAL, U/L LISTED, FUSED DISCONNECT OR CIRCUIT BREAKER IS REQUIRED
TO PROVIDE NEC OR CEC DISCONNECT AND OVERCURRENT PROTECTION.

B.)

MAXIMUM PERMISSIBLE AVAILABLE SYMMETRICAL RMS SHORT CIRCUIT POWER SUPPLY
CAPACITY: 5000A.

16>

When installing replacement power cubes, apply a very thin, uniform thickness film of DOW
#111 to mounting surface. Film is too thick if it squeezes out around power cube after pow-
er cube is torqued down. Start the mounting screws carefully into existing threads, and
then torque to 25 to 30 in-lbs.

17>

Set Auto Min. Speed with input on minimum, then set Auto Maximum Speed with input at maxi-
mum. Motor must not exceed its speed or voltage rating.

18>

Jumper for various process controllers.

19>

Remove jumper if Auto/Manual switch is used.

20>

Clip resistor (26.7K) and jumper (J2) when optional Dancer Position Adjust Pot. is
installed.

21>

Not associated with 232 Drive Thermostat circuit on Sh. 2. 232 is open in auto mode (“A”
not energized.)

22>

Numbers parenthesized are shown when different from original identification marking on kit.

23>

Cut jumpers (J1 & J2) if Remote Operator is installed.

DANGER

24>

EACH DRIVE MUST BE GROUNDED ACCORDING TO CODE REQUIREMENTS, USING THE DRIVE
“GND,” TERMINAL.

25>

The nominal Overload Threshold is 111% of rated current. With circuit tolerances, the
threshold can vary from 103% to 119%. The Overload Trip time is nominally 60 seconds with a
load current of 150% of rated current.

26>

The IET (Instantaneous Electronic Trip) threshold is set for a peak load current of 300%.

27>

For proper hardware and torque spec. see replacement parts table (special connector hard-
ware) sheet 8.

WARNING

28>

DRIVES ARE SHIPPED WITH 57 (OV) FLOATING, DEPENDING ON THE APPLICATION, 57 MAY
BE LEFT FLOATING, OR TIED TO EARTH GROUND. IF LEFT FLOATING, THE REGULATOR
CIRCUITS MAY RISE TO A HIGH POTENTIAL.

29>

If using an AC Tach, remove J1 & J2.

30>

Contact Rating: 125 VAC, 3 AMPS.

31>

Contact must be capable of breaking a 0.5 AMP, inductive load.

W/D 30070-1 (Sheet 11 of 13)