47

Table 7.B - Wire Specifications

Use in Controller

Type Conductor

RequiredCharacteristics

Acceptable Types

CONTROL WIRES

Remote Operator

Control Station:

D AUTO/MANUAL

D JOG/RUN

D FORWARD/REVERSE

D START/STOP

D Single conductor and/or

multiĆconductor

D Stranded copper

D AWG No. 16

D 600 VAC rating

D Insulation: polyvinyl

chloride (PVC)

D Temperature range:

40

°

-105

°

C (104

°

-221

°

F)

D Unshielded

D Any single conductor

meeting N.E.C. required

characteristics

SIGNAL WIRES

Remote Operator

Control Station:

D SPEED pot

D TORQUE pot

D Tachometer feedback

D Instrument Interface

D Voltage/Tachometer FolĆ

lower

D ThreeĆconductor

D Twisted with two twists per

inch

D TwoĆconductor

D Twisted pair with two twists

per inch

D Stranded copper

(19 x 29)

D AWG No. 16

D 600 VAC rating

D Twist per foot:

24 (1/2Ćinch lay)

D Insulation: polyvinyl

chloride (PVC)

D Temperature range:

40

°

-105

°

C (104

°

-221

°

F)

D User may twist single

conductors of required

specifications

D Reliance Part No.

417900Ć79X

D User may twist single

conductors of required

specifications.

D Reliance Part No.

417900Ć76EAD

TEST

METER

ADAPTER

KIT

(OPTIONAL)

INSTRUMENT INTERFACE/PRESET

SPEED KIT (OPTIONAL)

REMOTE OPERATORS

BUFFER KIT (STANDARD)

TACH FEEDBACK KIT (OPTIONAL)

Figure 7.2 - Three Phase FlexPak Plus Regulator Boardwith Some Typical Kits Installed

Advertising