47
Table 7.B - Wire Specifications
Use in Controller
Type Conductor
RequiredCharacteristics
Acceptable Types
CONTROL WIRES
Remote Operator
Control Station:
D AUTO/MANUAL
D JOG/RUN
D FORWARD/REVERSE
D START/STOP
D Single conductor and/or
multiĆconductor
D Stranded copper
D AWG No. 16
D 600 VAC rating
D Insulation: polyvinyl
chloride (PVC)
D Temperature range:
40
°
-105
°
C (104
°
-221
°
F)
D Unshielded
D Any single conductor
meeting N.E.C. required
characteristics
SIGNAL WIRES
Remote Operator
Control Station:
D SPEED pot
D TORQUE pot
D Tachometer feedback
D Instrument Interface
D Voltage/Tachometer FolĆ
lower
D ThreeĆconductor
D Twisted with two twists per
inch
D TwoĆconductor
D Twisted pair with two twists
per inch
D Stranded copper
(19 x 29)
D AWG No. 16
D 600 VAC rating
D Twist per foot:
24 (1/2Ćinch lay)
D Insulation: polyvinyl
chloride (PVC)
D Temperature range:
40
°
-105
°
C (104
°
-221
°
F)
D User may twist single
conductors of required
specifications
D Reliance Part No.
417900Ć79X
D User may twist single
conductors of required
specifications.
D Reliance Part No.
417900Ć76EAD
TEST
METER
ADAPTER
KIT
(OPTIONAL)
INSTRUMENT INTERFACE/PRESET
SPEED KIT (OPTIONAL)
REMOTE OPERATORS
BUFFER KIT (STANDARD)
TACH FEEDBACK KIT (OPTIONAL)
Figure 7.2 - Three Phase FlexPak Plus Regulator Boardwith Some Typical Kits Installed