U-gage, Analog q45ur remote ultrasonic sensors, Output response settings – Banner U-GAGE Q45UR Series—Analog User Manual

Page 3: Explanation of programmable output functions

Advertising
background image

Output Response Settings

IMPORTANT: Remove power before making any internal adjustments.

Using the two slots shown in Figure 1, a small flat-blade screwdriver may be used to
lift up and remove the black inner cover to expose the 4-position DIP switch (Figure 2).

Those switches are used to program the following functions:

U-GAGE

Analog Q45UR Remote Ultrasonic Sensors

P/N 59323 Rev. C

3

Banner Engineering Corp.

Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Switch

Function

1

Output Slope

Settings

2

Output Mode

ON = Current output enabled
OFF*= Voltage output enabled

3

Loss of Echo

ON = Min - Max Mode
OFF*= Hold Mode

4

Min - Max

ON* = Default to maximum output value
OFF = Default to minimum output value

ON = Output value increases with distance
OFF*= Output value decreases with distance

Explanation of Programmable Output Functions:

Switch 1: Output Slope Select

ON = (Direct) Output value (voltage or current) increases with increasing

distance of the target from the sensor

OFF* = (Inverse) Output value decreases with increasing distance of the

target from the sensor

Switch 2: Output Mode Select

ON = The 4 to 20mA current output (white wire) is enabled
OFF* = The 0 to 10V dc voltage output (black wire) is enabled

This switch configures the D/A driver to use either the current output or the voltage
output driver.

Switch 3: Loss of Echo Mode Select

ON = Min - Max Mode
OFF* = Hold Mode

This switch determines the output response to the loss of echo. The “Hold Mode”
(Switch 3 Off*) maintains the output at the value which was present at the time of
echo loss. The “Min - Max Mode” (Switch 3 On) drives the output to either the
minimum value (0V or 4mA or the maximum value (10V or 20mA) when the echo is
lost. Minimum or maximum value is selected by Switch 4.

Switch 4: Min - Max Default

ON* = Default to maximum output value at loss of echo
OFF = Default to minimum output value at loss of echo

Switch 4 selects the output response to loss of echo when “Min - Max Mode” is
selected by Switch 3 (see above).

* Factory default setting

0

Near

Window

Far

Window

10

Target Position

Analog Output (V dc)

Positive

Slope

Voltage/Current-Sourcing Models

4

20

Analog Output (mA)

Figure 3. Output as a function of target

position