Analog Q45UR Series Specifications

Indicators

Performance Specifications

* Resolution and linearity are

specified using a 50 mm x
50 mm (2" x 2") aluminum
plate at 22ºC under fixed
sensing conditions using the
4-20 mA output @15V dc.

Range for Nominal Sensing
Position

Near Limit: 50 mm (2") min.
Far Limit: 250 mm (10") max.

Supply Protection Circuitry

Protected against reverse polarity and transient voltages

Output Configuration

One voltage sourcing and one current sourcing; one or the other output is enabled by internal
programming switch #2 (see page 2).

Output Rating

Voltage Sourcing: 0 to 10V dc, 10mA maximum
Current Sourcing: 4 to 20mA, 1 to 500 ohm impedance

Output Protection Circuitry

Both outputs are protected against continuous overload and short circuit

Supply Voltage and Current

15 to 24V dc (10% maximum ripple) at 100 mA, exclusive of load

Adjustments

Push-button TEACH-mode programming of window limits (see page 2)
The following may be selected by a 4-position DIP switch located on top of the controller, beneath the
transparent acrylic and black inner covers (see page 2)

Switch 1: Output slope: output value increases or decreases with distance
Switch 2: Output mode: current output or voltage output
Switches 3&4: Response to loss of echo: (see page 3)

Response Speed Adjustment: Single-turn potentiometer selects six response values from 10 to 320
milliseconds (see page 3)

Resolution*:

0.2% of sensing distance at 320 ms response
0.4% of sensing distance at 10 ms response

Linearity*:

±1.0 mm (0.04") with 100 to 200 mm sensing window
±2.0 mm (0.08") with 50 to 250 mm sensing window

Temperature stability: ±0.03% of sensing distance per ºC from 0 to 50ºC (±0.05% per ºC over remainder

of operating temperature)

Ultrasonic beam angle: ±3.5º

Also see response curve on page 5

Minimum target size is specified as a 10 x 10 mm (0.4" x 0.4") aluminum plate (at any point within the 50 to
150 mm sensing range).

Construction

Controller: Molded thermoplastic polyester housing, o-ring sealed transparent acrylic top cover, and

stainless steel hardware

Sensors:

M18C2.0: Stainless steel M18 threaded barrel housing and jam nuts, ULTEM

®

polyetherimide

front cover, ceramic transducer, TEXIN

®

polyurethane rear cover

S18C2.0: Thermoplastic polyester S18 threaded barrel housing and jam nuts, ULTEM

®

polyetherimide front cover, ceramic transducer, TEXIN

®

polyurethane rear cover

Q13C2.0: Molded 30% glass reinforced thermoplastic polyester housing, ceramic transducer,

fully epoxy-encapsulated

Environmental Rating

Controller:

IEC IP67; NEMA 6P

Sensor:

IEC IP65; NEMA 4

Three status LEDs:
Green ON steady

= Power to controller is ON

Green flashing

= Current output fault detected (indicates that the 4-20 mA current path to ground

has been opened)

Yellow ON steady

= Target is sensed within the window limits (Yellow LED also indicates

programming status during setup mode)

Red flashing

= Relative strength of received echo

5-segment moving dot LED indicates the position of the target within the sensing window

ULTEM

®

is a registered trademark of General Electric

TEXIN

®

is a registered trademark of Bayer Corporation

D