U-gage – Banner U-GAGE Q45U Series—Analog User Manual

Page 2

Advertising
background image

1

ON

2

3

4

Switch #2

OFF = ON/OFF

ON = HI/LOW

See Table Below for

Programming Information

U-GAGE

Q45U Ultrasonic Sensors with Bipolar Discrete Outputs

2

P/N 44177 Rev. D

Banner Engineering Corp.

Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

Near and Far Sensing Limit Settings:
The Q45U features a single push button for programming of
sensing window near and far limits (Figure 1). See the
programming procedure on page 4.

Status Indicators:
Status indicator LEDs are visible through the transparent, o-ring
sealed Lexan® top cover. Indicator function in the RUN mode
is, as follows:

• The green LED is on steadily whenever power is applied to the
sensor, and flashes to indicate an overloaded output.

• The red LED lights when an echo is received, and flashes at a
rate that is proportional to echo strength.

• The yellow LED lights whenever the outputs are conducting.

The 5-segment moving dot LED indicator displays the relative
position of the target within the programmed sensing window.
The #1 LED flashes when the target is closer than the near limit.
The #5 LED flashes when the target is beyond the far limit.

Output Response Settings:
IMPORTANT: Remove power before making any internal
adjustments.

Using the two slots shown in Figure 1, a small flat-blade
screwdriver may be used to lift up and remove the black inner
cover to expose the 4-position DIP switch (Figure 2). Those
switches are used to program the following functions:

Limits

N

1 2 3 4 5

Green POWER
Indicator

Red SIGNAL
Indicator

Yellow OUTPUT
Indicator

Push button for

Programming of Sensing

Window Limits

5-Segment Target

Position Indicator

(N = Near)

Slots for Inner
Cover Removal

Figure 1.

Q45U Features

Figure 2.

Q45U Programming Switches

Switch

Function

1

ON/OFF Mode
Output: On = normally closed (output energizes when target is absent)

Off* = normally open (output energizes when target sensed)

2

Mode:

On = HIGH/LOW (fill level control, see description, on page 3)
Off* = ON/OFF (output follows sensing action)

3 - 4

Response (20 ms/cycle)

Switch 4

Switch 3

1 Cycle
2 Cycles
8 Cycles*
32 Cycles

Off

On

Off

On

*Denotes factory settings.

NOTE: Response setting of 2 cycles, or higher, is recommended for optimum sonic and electrical noise immunity. Always use the

slowest acceptable response speed for your application. Single cycle update is only recommended for short range
(<50 cm) applications looking for a stationary target (i.e. reflector).

HIGH/LOW Mode
On = Pump Out
Off = Pump In

Off
Off

On
On