U-GAGE

Q45U Ultrasonic Sensors with Bipolar Discrete Outputs

P/N 44177 Rev. D

3

Banner Engineering Corp.

Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

The HIGH/LOW mode (switch #2 on) provides the switching logic required for fill-level, web tensioning control, and similar
applications. In the HIGH/LOW mode, the output energizes when the target reaches the first sensing window limit, and stays
energized until the target moves to the second limit. The output then de-energizes at the second limit and does not re-energize until
the target moves, again, to the first limit. Figure 3 shows how pumping action might be controlled, directly, by the sensor in a fill-
level application.

;;

;;

;;

;;

Sensor

High Level (Near Limit)

Pump-in Application

(switch #1 off)

Pump-out Application

(switch #1 on)

Low Level (Far Limit)

Initial Level

1

Initial Tank Level - Outputs are INACTIVE

2

3

Level Drops Below Far Limit - Outputs ACTIVE

Level Rises Above Near Limit - Outputs DEACTIVATE

2

1

3

Flow

Flow

1

Initial Tank Level - Outputs are INACTIVE

2

3

Level Rises Above Near Limit - Outputs ACTIVE

Level Drops Below Far Limit - Outputs DEACTIVATE

;;

;;

;;

;;

Sensor

Pump Control

High Level (Near Limit)

Low Level (Far Limit)

Initial Level

3

1

2

Figure 3.

High/Low Level Control (switch #2 on)

NOTE: If no echo is received by the sensor, the target is assumed to be beyond the far window limit.