Dynamic TEACH

Darkest

(no signal)

Most Light

(saturated

signal)

Output OFF

Output ON

Darkest Presented

Condition

Lightest Presented

Condition

Sensor positions

threshold between

presented conditions

Figure 4. Dynamic TEACH (Light Operate shown)

Dynamic TEACH sets a single switching threshold

(switchpoint).

Dynamic TEACH is used to teach during actual

sensing conditions, taking multiple samples of the

light and dark conditions and automatically setting

the threshold at the optimum level.

The Output ON state (Light- or Dark-Operate

setting) remains as it was last configured. To

change the Light-/Dark-Operate setting, see

Sensor

Setup

on page 3.

Dynamic TEACH is recommended for applications

where a machine or process may not be stopped for

teaching.

1. Access the Dynamic TEACH mode.

Method

Action

Result

Push Button

Press and hold the push button for longer

than 4 seconds.

Power LED Indicator: OFF

Output LED Indicator: Quick flash

(2 Hz)

Remote Line Hold the remote line low (to ground) for

longer than 2 seconds.

2 seconds

2. Teach the sensing condition.

Method

Action

Result

Push Button

Continue to hold the push button and present

the Output ON and OFF conditions multiple

times.

Power LED Indicator: OFF

Output LED Indicator: Quick flash

(2 Hz)

Remote Line

Continue to hold the remote line low (to

ground) and present the Output ON and OFF

conditions multiple times.

3. Return to Run mode.

Method

Action

Result

Push Button

Release the push button.

TEACH Accepted
Power LED Indicator:
Flashes 3

times, then solid green

Output LED Indicator: OFF4, then

ON or OFF depending on the output

state

The sensor returns to Run mode with

the new settings.

TEACH Not Accepted
Power LED Indicator:
Flashes 3

times, then solid green

Output LED Indicator: ON4, then

ON or OFF depending on the output

state

The sensor returns to Run mode

without changing settings.

Remote Line Release the remote line/switch.

4 The initial output LED indicator condition is simultaneous with the power LED indicator 3-flash

WORLD-BEAM

®

QS18E Series

P/N 136564 Rev. C

www.bannerengineering.com - tel: 763-544-3164

5