Modbus register block baseline – Banner SureCross DX80 Wireless M-GAGE Node User Manual

Page 3

Advertising
background image

P/N 131598 rev. F

3

Banner Engineering Corp. • Minneapolis, MN U.S.A

www.bannerengineering.com • Tel: 763.544.3164

SureCross™ DX80 M-GAGE™ Node with Integrated Battery

There are sixteen Modbus holding registers
for each device. Calculate the holding
register number for each device using the
equation:

Register number = I/O# + (Node# • 16).

Because the Gateway is always device 0, the
Gateway’s holding registers are registers 1
through 16 while registers for Node 1 are 17
through 32.

Using the equation, the register number for
I/O point 15 for Node 7 is 127.

The M-GAGE value in I/O 1 is the deviation
between the total measured magnetic field in
the X, Y, and Z axes and the stored baseline.

To send configuration messages, use the
Node’s I/O point 13.

To create a baseline command, use a control
message or use the Node’s I/O point 14.
For more instructions, refer to the Baseline
section.

I/O

Point

Gateway

Modbus

Holding

Register

Node

Modbus

Register

DX80

M-GAGE™ FLEX(Node)

1

1

1 + (Node# × 16)

M-GAGE

2

2

2 + (Node# × 16)

3

3

3 + (Node# × 16)

4

4

4 + (Node# × 16)

5

5

5 + (Node# × 16)

6

6

6 + (Node# × 16)

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

10

10

10 + (Node# × 16)

11

11

11 + (Node# × 16)

12

12

12 + (Node# × 16)

13

13

13 + (Node# × 16)

Configuration Message

14

14

14 + (Node# × 16)

Baseline Command

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Modbus Register Block

Baseline

The baseline function of the M-GAGE Node stores the ambient magnetic field values of the X, Y, and Z axes as a baseline reading. Once this
baseline is established, any deviation in the magnetic field will be reflected in the M-GAGE register. The more disruption in the magnetic field,
the larger the M-GAGE register value.

For a host-connected system using standard Gateways, set the baseline magnetic field by writing to a Modbus register. Sending the value of
4096 (0x1000) to the Node’s I/O point 15 (Control Message) triggers the M-GAGE to read the existing magnetic field as the new baseline.

For non-host connected systems, use one of the two special M-GAGE Gateways to set the baseline:

The inputs of the DIP switch M-GAGE Gateway (model DX80G*M6*6P6ZP) are mapped to the M-GAGE Node’s I/O point 14. Activating

the Gateway’s input for at least five seconds triggers the M-GAGE to use the existing magnetic field as the new baseline.
The special M-GAGE Gateway (model DX80G*M6*6P6Z) uses special mapping to baseline up to six M-GAGE Nodes.