Sending the configuration message to register 13 – Banner SureCross DX80 Wireless M-GAGE Node User Manual

Page 7

Advertising
background image

P/N 131598 rev. F

7

Banner Engineering Corp. • Minneapolis, MN U.S.A

www.bannerengineering.com • Tel: 763.544.3164

SureCross™ DX80 M-GAGE™ Node with Integrated Battery

Modbus Register 13

Low Pass Filter

Sample High

Counter

Report

Rate

Sample Rate

Baseline

Filter

Threshold and

Hysteresis

Device Settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Filter Off

0

1

Filter Threshold 30, 2 Hour

1

0

Filter Threshold 30, 8 Hour

1

1

Threshold

Hysteresis

No Change

0

0

0

50

15

0

0

1

100

30

0

1

0

150

30

0

1

1

200

30

1

0

0

300

40

1

0

1

500

50

1

1

0

800

60

1

1

1

Sending the Configuration Message to Register 13

Modbus command 06 (write single holding register) is used in this example to set the parameter values for the M-GAGE Node. A sample
configuration message for Node 1:

Modbus Register 13

Low Pass Filter

Sample High

Counter

Report

Rate

Sample Rate

Baseline

Filter

Threshold and

Hysteresis

Bits

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Values

0

0

0

0

1

0

1

1

0

1

0

0

1

1

0

1

Hex Values

0

B

4

D

Sending this configuration message to register 13 sets the low pass filter to “no change;” the sample high counter to 2; the report rate and
sample rate to 125 milliseconds; the baseline filter to 0, 15; the threshold to 300; and the hysteresis to 40.

The complete Modbus command, in hexidecimal, is:

Slave ID#

Modbus

Command

Register Number

Configuration Value

01

06

00

1C

0B

4D

CRC

CRC

Configuration Using Registers 7, 15, and 16

To send Modbus configuration commands to registers 7, 15, and 16, please refer to the Modbus Host Configuration Reference Guide, Banner
document number 132114 for instructions and example commands.