Banner U-GAGE QT50U DC Series—Analog User Manual

Page 3

Advertising
background image

Switch Function

Settings

OFF = Hold Mode

3

Min-Max

ON = Default to maximum output value on loss of echo

OFF* = Default to minimum output value on loss of echo

4

Teach/Enable Control

ON* = Configured for remote teach

OFF = Configured for enable

5 and 6 Analog Voltage Output Response for 95%

of Step Change

Switch 5

Switch 6

100 ms with 100 ms update

OFF

OFF

500 ms with 100 ms update*

ON*

OFF*

1100 ms with 100 ms update

OFF

ON

2300 ms with 100 ms update

ON

ON

7

Temperature Compensation

ON* = Enabled

OFF = Disabled

8

Factory Calibration

ON = For factory calibration only; switch should be set to OFF for use

OFF* = DIP-switch settings in control

* Factory default setting

DIP Switch Selectable Functions

CAUTION: To avoid damage to the sensor caused by static discharge (ESD), observe proper ESD

precautions (grounding) while adjusting the DIP switches.

Switch 1: Output Mode Select

ON = 4 to 20 mA current output is enabled
OFF = 0 to 10 V dc voltage output is enabled

Switch 1 configures the sensor internally to use either the current output or voltage output configuration.

Switch 2: Loss of Echo Mode Select

ON = Min-Max Mode
OFF = Hold Mode

Switch 2 determines the output response to the loss of echo. “Min-Max Mode” (Switch 2 ON) drives the output to either

the minimum value or the maximum value when the echo is lost. (Minimum or Maximum value is selected via Switch 3.)

“Hold Mode” (Switch 2 OFF) maintains the output at the value which was present at the time of echo loss.

Switch 3: Min-Max Default

ON = Default to maximum output value at loss of echo (10.5 V dc or 20.8 mA)
OFF = Default to minimum output value at loss of echo (0 V dc or 3.6 mA)

Switch 3 selects the output response to loss of echo when “Min-Max Mode” is selected via Switch 2. When Switch 2 is OFF,

Switch 3 has no function.

Switch 4: Teach/Transmit Enable Control

ON = Gray (or yellow) wire configured for remote teach
OFF = Gray (or yellow) wire configured for transmit enable/disable: High (5 to 30 V dc) - Transmit Enabled (Power LED

solid Green); Low (0 to 2 V dc) - Transmit Disabled (Power LED flashes at 2 Hz)

When Switch 4 is ON, the gray wire is used to teach window limits to the sensors.

When Switch 4 is OFF, the gray wire is used to enable and disable the sensor’s transmit burst. The sensor output will react

as if a “loss of echo” occurred and either hold the output or change to minimum or maximum value (depending on switch 2

and 3 settings). This function may be used when multiple sensors are in close proximity, which may make them vulnerable

to crosstalk interference. A PLC can be used to enable the sensors one at a time to avoid crosstalk.

Switches 5 and 6: Response Speed Adjustment

U-GAGE QT50ULB Series Sensors with Analog Output

P/N 70137 Rev. B

www.bannerengineering.com - tel: 763-544-3164

3