Sensor programming – Banner U-GAGE QT50U DC Series—Analog User Manual

Page 4

Advertising
background image

Switches 5 and 6 are used to set the speed of the output response. The four values for response speed relate to the

number of sensing cycles over which the output value is averaged.

Switch 7: Temperature Compensation

ON = Temperature compensation enabled
OFF = Temperature compensation disabled

Changes in air temperature affect the speed of sound, which in turn affects the distance reading measured by the sensor.

An increase in air temperature shifts both sensing window limits closer to the sensor. Conversely, a decrease in air

temperature shifts both limits farther away from the sensor. This shift is approximately 3.5% of the limit distance for a 20

°C change in temperature. With temperature compensation enabled (Switch 7 ON), the sensor will maintain the window

limits to within 1.8 percent over the –20 °C to 70 °C range.

The temperature sensor in the sensor’s bezel cannot adapt to temperature change as quickly as an external temperature

device can. When there are fast fluctuations in temperature, it may be best to use an external temperature monitor and

feed its signal and the uncompensated distance measurement into a controller and perform the compensation calculations

within the controller.

Consult the factory for details on performing temperature compensation calculations.

If temperature compensation is enabled, exposure to direct sunlight can affect the sensor’s ability to accurately

compensate for changes in temperature.

With temperature compensation enabled, the temperature warmup drift upon power-up is less than 0.8% of the

sensing distance. After 15 minutes, the apparent distance will be within 0.5% of the actual distance. After 30

minutes, the apparent distance will be within 0.3% of the actual distance.

Switch 8: Factory Calibration

ON = Factory calibration only
OFF = Normal operation

U-GAGE

MIN

SIGNAL

TM

MAX

POWER

ANALOG

WINDOW

LIMIT

MIN

ANALOG

MAX

Figure 4. Sensor Features

MIN - Minimum limit indicator
MAX - Maximum limit indicator
POWER - Sensor power indicator
SIGNAL - Target signal strength indicator

General Notes on Programming

The sensor returns to RUN mode if the limit is not registered within 120 seconds after entering TEACH Mode.

Press and hold the programming push button for more than 2 seconds (before teaching the limit) to exit PROGRAM

mode without saving any changes. The sensor will revert to the last saved program.

If the push buttons do not respond, perform a remote lockout procedure to enable push buttons.

Sensor Programming

Two TEACH methods may be used to program the sensor:

Teach individual minimum and maximum limits

Use the Auto-Window feature to center a sensing window around the taught position

The sensor may be programmed either via its two push buttons, or via a remote switch. Remote programming also may be

used to disable the push buttons, preventing unauthorized personnel from adjusting the programming settings. To access

this feature, connect the gray wire of the sensor to 0–2 V dc, with a remote programming switch between the sensor and

the voltage.

NOTE: The impedance of the Remote Teach input is 12 kΩ.

Programming is accomplished by following the sequence of input pulses. The duration of each pulse (corresponding to a

push button “click”), and the period between multiple pulses, are defined as “T” where 0.04 seconds < T < 0.8 seconds.

U-GAGE QT50ULB Series Sensors with Analog Output

4

www.bannerengineering.com - tel: 763-544-3164

P/N 70137 Rev. B