Caution typical wiring – SARGENT 2900 Fire Guard Electromechanical Closer-Holder User Manual

Page 3

Advertising
background image

A7395C

3

CAUTION

Typical Wiring

1. DISCONNECT ALL POWER BEFORE BEGINNING INSTALLATION

TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE

2. INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE

PERSON

Stand-Alone Units 2960

• Wire stand-alone unit to appropriate

power supply and fire alarm

• Refer to data sticker for proper

input voltage and current specifications

• Energize power supply

• Open door to hold-open point

Door should hold open

• Depress On/Off Switch. Door should

close and latch

• Adjustment of spring power may be

necessary to ensure proper latching

• Depress on/off switch again. Open door to

hold open position; door will hold open.

3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL

ELECTRICAL CODES, ORDINANCES AND REGULATIONS

4. MAXIMUM WIRE SIZE IS 18AWG

CAUTION: Input power supply must match circuit

board voltage rating, either 24VAC/DC or 120VAC.

Opening for

Concealed Wiring

Earth Ground

Negative (-)

Positive (+)

3

2

1

Appropriate

Power Supply

Data

Sticker

On/Off

Switch

Terminal Strip

for Power Input Connections

Optional remote

release connection

Copyright © 2011, Sargent Manufacturing Company, an ASSA ABLOY Group