Sample Wiring #2 – TL- (SARGuide) with 12- 58- (Electric Dogging)
combination and 3532 Power Supply with Battery Back-up. 53-,
55- wiring if required.

System Description:
SARGuide is always powered. During a
power outage SARGuide remains powered
and illuminated by 3532 battery back-up
power.

Fire Rated Operation:
If using 12-58- Electric Dogging in
conjunction with SARGuide, a normally
closed fire alarm contact (by others) must
be used and must be wired as shown.

Notes:
1. TL- SARGuide power requirement:

Input Power: 24VDC/VAC
Current draw: 30mA

2. Pigtail assemblies, electric hinge, raceway

and rail connector terminations and wire
colors all match.

3. For 53, 55- and 58- wiring also refer to

individual product instructions provided.
Wire as required by rail type used.

F. TL- SARGuide Wiring Examples cont’d

4

Electric hinge with

8 & 4-pin connectors

Raceway harness with

8 & 4-pin connectors.

Pigtail harness #1

assembly with

8-pin connector

80 series rail prefixes
53- latch bolt monitor swicth
55- signal switch
58- electric dogging

Pigtail harness #2

assembly with

4-pin connector

1

4

2

3

12-TL- 58- 80 Series

Rail with 8 & 4-pin

connectors

EXIT EXIT EX

IT

2, Grey

(TL +24)

1, Violet

(TL

-

24)

120 VAC

L/N/G

L N

Input

120VAC 60HZ

+ - + -

Output

1

Output

2

1 2 3 4 5 6 7 8 9

TB1

TB2

TB3

+

-

Battery

Battery

3532
24VDC, 2Amp
Power Supply
w/Battery Backup

GND

58- (+24) Red, 2

1

7

5

6 4

3

2

8

58- (-24) Black, 1

53- (NC) Orange, 5

53- (C) White, 3

53- (NO) Green, 4

55- (NC) Brown, 8

55- (C) Blue, 6

55- (NO) Yellow, 7

Normally

Closed

Fire Alarm

Connection

By Others

24VDC