Edit shutdown configuration – Dell UPS 1000T User Manual

Page 35

Advertising
background image

Configuration

35

1 In the Power source field, select the UPS that powers the computer hosting the Dell ULNM.

NOTE:

This settings is also accessible through

Settings > Auto-Discovery > Set as Power Source

.

2 Change parameters as needed.
3 Click Save.

Source Parameter

The Power source value is the IP address of the UPS that powers the computer hosting the Dell ULNM.

Shutoff Parameter

The load segment value is the load segment that powers the server hosting Dell UPS Local Node

Manager, when available.
WARNING:

NOT available through USB connection and in shutdown controller mode

NOTE:

When “Master” is selected, the entire UPS will switch off.

Access Parameters

Access parameter are used when the Power Source is managed through the network.
If the Power Source is an Ethernet card (Dell Network Management Card H910P), a login and password

are needed in order to synchronize the settings between the Dell ULNM and the Dell Web/SNMP Card,

such as when changing the shutdown duration value.
NOTE:

If this synchronization is not provided, the system will have conflicting instructions on power events. If the Power

Source is another Dell ULNM with the shutdown controller feature activated, then login and password are

mandatory. The Login must be the “admin” account.

Edit Shutdown Configuration

To configure Shutdown Parameters:
NOTE:

The “Edit shutdown configuration” window opens automatically when the power source is set.

1 Login with an administrator user profile.
2 Select Settings > Shutdown. The Shutdown page is displayed.
3 Click Edit shutdown configuration.The Edit Shutdown Configuration dialog box displays (see

Figure 18).

4 Change parameters as needed.
5 Click Save.

0120_3-Dell ULNM UG.book Page 35 Saturday, November 2, 2013 5:34 PM