Use Case 4

Typical example with four computers. According to the servers' roles, you may want to shut down the

servers at different times:

Computer hosting Dell ULNM#1 is directly attached to the UPS (USB/Serial). The Shutdown

Controller must be installed on the server that will be the last one to shut down.

NOTE:

On Pulsar series, this computer must be powered by the master outlet.

Computer hosting Dell ULNM#2 requires a long delay to shutdown, such as hosting database or

VMware.

Computer hosting Dell ULNM#3 must be the last one to be shutdown because other servers depend

on it, such as File server.

Computer hosting Dell ULNM#4 is another server that must be stopped before computer 2 or 3

(Web server), or this computer can also be stopped for load shedding purposes (workstation).

The recommended configurations are:

• On Dell ULNM#1: Configure Shutdown Timer to None and Shutdown Duration to 120s.
• On Dell ULNM#2: Configure Shutdown Timer to 180s and Shutdown Duration to 180s.
• On Dell ULNM#3: Configure Shutdown Timer to None and Shutdown Duration to 120s.
• On Dell ULNM#4: Configure Shutdown Timer to 120s and Shutdown Duration to 120s.

The following time diagram summarizes this configuration (see Figure 27):

Figure 27. Shutdown Controller Diagram