ACCELERA® 300 HEAT PUMP WATER HEATER |

19

INSTALLATION

INSTALLATION

Air flow

Air flow

CAUTION :

Risk of electric shock

Use copper conductors only

11

10

4

6

3

1

16

15

13

12

8

7

14

9

5

26

_03

_01

_14

06

2

 

CAUTION :

Risk of electric shock
Use copper conductors only

1 Capacitor

2 Cable entry into the water heater casing

3 Strain relief (cable clamp)

4 Mains terminal

5 Frost monitor

6 Heat pump control thermostat

7 Fan motor

8 Heat pump terminal

9 Thermostat, booster heater

10 High limit safety cut-out, booster heater,

manual reset (see 14.1.1)

11 Booster heater

12 Sacrificial anode

13 Safety pressure limiter, manual reset,

(see 14.1.2)

14 Condensate pan drain

15 Compressor

16 Compressor motor protection (Klixon),

delay auto reset (see 14.1.3)

» Pull the power cable through the cable entry into the water

heater interior.

» Route the power cable through the strain relief (cable

clamp).

» Connect the power cable to the mains terminal in accordance

with the wiring diagram (see chapter 16.2 "Wiring Diagram".

L1, L2 and ground).

WARNING Electric shock

Risk of injury through inadequate grounding.

»

Ensure that the water heater is correctly grounded

in accordance with the requirements at the place of

installation.

The ground conductor of the power cable must be

connected to the terminal marked G or Earth.

10.8.1 High limit safety cut-out

At ambient temperatures below -10 °C (14 °F), for example during

shipping or in storage, the high limit safety cut-out may trip.
Press the reset button of the high limit safety cut-out to reset it.

To do this, first remove the water heater cover.

1

26

_03

_01

_11

51

1 Reset button for high limit safety cut-out