Parameters of Commands and Responses

Control outputs

This parameter is used with communication command "MS" and DRQ input. Specify whether the
control outputs (HIGH/LOW/GO outputs) are on or off using a one-digit value (ASCII character).

Error numbers

The following table lists the error numbers that are returned as error responses when errors occur in
the communication between DL-RS1A and GT-70A Series sensor amplifiers.
Each error number is identified with two digits (ASCII characters).

Control output

Description

0

All control outputs are off

1

Only HIGH output is on

2

Only LOW output is on

3

Both HIGH and LOW outputs are on

4

Only GO output is on

Error

number

Error name

Problem

Action

00

Invalid command

error

An invalid command was

received.

Make sure that the external device has

sent a command listed in

"Communication commands" (page 10).

20

Data length error

Data with the correct length was

not received.

Make sure that the external device has

sent either "CR" or "CR + LF" as a data

delimiter.

21

Number of

parameters error

The correct number of parameters

for the command was not

received.

Make sure that the number of parameters

and the positions of the commas used as

data delimiters conform to the command

format shown in "Commands and

Responses" (page 7).

22

Parameter error

·

A parameter exceeds its range

of value.

·

The external device is trying to

write a data type that cannot be

written.

·

The external device is trying to

read a data type that cannot be

read.

·

The data format is incorrect.

Make sure that the external device is

sending a command listed in

"Communication commands" (page 10).

29

Communication error

An error was detected with

RS-232C communication.

Make sure that DL-RS1A and the external

device have the same communication

settings configured. For information on

configuring DL-RS1A, refer to "(1)

Communication setup switches" (page 2).

65

ID number error

The ID number specified with the

command is incorrect.

Make sure that the sent data specified as

the ID number is a 2-digit number (ASCII

characters) according to the number of

connected units.

Parameters of Commands and Responses

The commands are only sent and received when a response is returned from DL-RS1A to the
external device within 500 ms.
Take the appropriate action to resolve the problem by referring to "Troubleshooting" (page 17).

66

Expansion line error

The communication could not be

established due to a problem with

an expansion line.

Check that each of the sensor amplifiers

and DL-RS1A are securely and properly

connected by referring to "Connecting

the Unit to Sensor Amplifiers" (page 3).

Make sure that sensor amplifiers that are

supported by DL-RS1A are connected

(refer to page 4).

67

Write control error

DL-RS1A is not writable.

Change the read/write setting switch to

the R/W position to enable writing to DL-

RS1A. For information on the read/write

setting switch, refer to "Part Names and

Functions" (page 2).