Gas Supply Specifications.

2.7.1

The gas supply input specifications to the unit for Natural Gas are as follows:

Natural Gas - The maximum static pressure to the unit must not exceed 14” W.C.. The gas

supply pressure to the unit must be of sufficient capacity to provide 1500 cfh while

maintaining the gas pressure at 4.0 inches W.C. for FM, or 4.2 inches W.C. for IRI gas

trains.
Propane - The maximum static pressure to the unit must not exceed 14” W.C.. The gas

supply pressure to the unit must be of sufficient capacity to provide 600 cfh while

maintaining the gas pressure at 4.0 inches W.C. for FM, or 4.2 inches W.C. for IRI gas

trains.

The maximum static pressure to the unit must not exceed 14” W.C.. The minimum operating

gas pressure for natural gas is 4 inches W.C. for both FM and IRI gas trains when the unit is

firing at maximum input. The gas supply pressure to the unit must be of sufficient capacity to

provide 1500 cfh while maintaining the gas pressure at 4 inches W.C. for FM or IRI gas trains.

Manual Gas Shutoff Valve

2.7.2

A manual shut-off valve must be installed in the gas supply line upstream of the Boiler as shown

in Figure 2-6. Maximum allowable gas pressure to the Boiler is 14” W.C.

NATURAL

GAS

SUPPLY

PROPANE

SUPPLY

1-1/2" MANUAL

SHUTOFF

VALVES

DIRT

TRAPS

Figure 2-6: Manual Gas Shut-Off Valve Locations