10 i/o box connections, 1 outdoor sensor in (1), Benchmark 1.5ln dual-fuel low nox boiler – AERCO BMK 1.5 LN Dual Fuel Feb 2013 User Manual

Page 22: Gf-121

Advertising
background image

CHAPTER 2: INSTALLATION

Page

22 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Figure 2-10. I/O Box Terminal Locations and Functions

2.10 I/O BOX CONNECTIONS

The types of input and output signals and devices to be connected to the I/O Box terminals

shown in Figure 2-10 are described in the following paragraphs.

NOTE

Older I/O PCBs are wired the same as new ones, even if silk-

screen designations may slightly differ.

CAUTION

DO NOT make any connections to the I/O Box terminals labeled

“NOT USED”. Attempting to do so may cause equipment

damage.

Outdoor Sensor In (1)

2.10.1

An outdoor air temperature sensor (AERCO Part No. 122790) will be required primarily for the

Indoor/Outdoor reset mode of operation. It can also be used with another mode if it is desired to

use the outdoor sensor enable/disable feature. This feature allows the boiler to be enabled or

disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an

enable/disable outdoor temperature, see the Configuration menu in Chapter 3.
The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the

OUTDOOR SENSOR IN and SENSOR COMMON terminals in the I/O Box (see Figures 2-9 and

2-10). Wire the sensor using a twisted shielded pair wire from 18 to 22 AWG. There is no

polarity to observe when terminating these wires. The shield is to be connected only to the

Advertising