CHAPTER 3: CONTROL PANEL OPERATION

Page

42 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Table 3-7:

Relationship Between Air/Fuel Valve Position and Energy Input For Unit

Running On Natural Gas

Air/Fuel Valve

Position (% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input

(% of Full Capacity)

0%

0

0

10%

0

0

16%

(Stop Level)

75,000

5.0%

20%

157,000

10%

30%

310,000

21%

40%

534,000

36%

50%

783,000

52%

60%

970,000

65%

70%

1,140,000

76%

80%

1,240,000

83%

90%

1,370,000

91%

100%

1,500,000

100%