7 condensate drain trap, Benchmark 1.5ln dual-fuel low nox boiler, Gf-121 – AERCO BMK 1.5 LN Dual Fuel Feb 2013 User Manual

Page 87

Advertising
background image

CHAPTER 7: MAINTENANCE

PR2: 05/09/12 Page

87 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

7.7 CONDENSATE DRAIN TRAP

The Benchmark 1.5 Boiler contains a condensate trap as shown in Chapter 2, Figure 2-5. The

trap is located external to the unit and attached to the drain pipe from the exhaust manifold. This

trap should be inspected and, if necessary, cleaned to ensure proper operation.

NOTE

There are two slightly different types of condensate traps that may

be used in your configuration; an older style without an inlet

adapter, and a newer style with a built-in adapter (see Figure 7.5).

Maintenance is the same, except that the newer style does not

need an orifice gasket (Step 6).

To inspect and clean the trap, proceed as follows:

1. Disconnect the external condensate trap by loosening the union pipe connection between

the trap and the exhaust manifold drain pipe.

2. Remove the connections on the inlet and outlet sides of the condensate trap shown in

Figure 7-5.

3. Loosen the four (4) thumbscrews securing the cover on the condensate trap. Remove the

cover.

4. Remove the float from the condensate trap.
5. Remove the orifice gasket from the trap (note that newer style trap does not use or need

an orifice gasket).

6. Thoroughly clean the trap, float and gasket. Also inspect the drain piping for blockage. If

the trap cannot be thoroughly cleaned, replace the trap.

7. After the above items have been inspected and thoroughly cleaned, replace the orifice

gasket and float in the condensate trap and replace the trap cover.

8. Reassemble all piping and hose connections to the condensate trap inlet and outlet.

Reconnect trap to exhaust manifold drain.

Advertising