1 bms external field wiring, 2 bms setup and startup, 7 combination control system (ccs) – AERCO BMK 1.5 LN Dual Fuel Feb 2013 User Manual

Page 64: Benchmark 1.5ln dual-fuel low nox boiler, Gf-121

Advertising
background image

CHAPTER 5: MODE OF OPERATION

Page

64 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

BMS External Field Wiring

5.6.1

Wiring connections for BMS control using PWM signaling are made between connector JP2

on the BMS panel (boilers 1 through 8), and the B.M.S. (PWM) IN terminals in the I/O Box

on the front of the boilers. Refer to the wiring diagram provided on the cover of the I/O Box.
Wiring connections for RS485 Modbus control are made between connector JP11 on the

BMS (boilers 9 through 40) or JP6 on BMS II/ACS (boilers 1-32) and the RS485 COMM

terminals in the I/O Box on the front of the boilers.
Wire the units using shielded twisted pair wire between 18 and 22 AWG. Observe the

proper polarity for the B.M.S. (PWM) IN and/or RS485 COMM wiring connections. Shields

should be terminated only at the BMS/BMS II/ACS and the boiler end must be left floating.

Each unit’s wiring must conform to the above.

BMS Setup and Startup

5.6.2

This mode of operation is factory preset and the AERCO BMS/BMS II/ACS controls the

firing rate (air/fuel valve % open position). There are no setup instructions for each

individual unit.
To operate the unit in manual mode, press the

AUTO/MAN switch. The REMOTE LED will

go off and the

MANUAL LED will light

To change back to the BMS mode, simply press the

AUTO/MAN switch. The REMOTE

LED will again light and the

MANUAL LED will go off.

5.7 COMBINATION CONTROL SYSTEM (CCS)

NOTE

Only the BMS and ACS can be utilized for the Combination

Mode, but not the BMS II.

A Combination Control System (CCS) is one that uses multiple boilers to cover both space-

heating and domestic hot water needs. An AERCO Boiler Management System (BMS)

Model 168 and a Combination Control Panel (CCP) or an ACS and an ACS Relay Panel

(optional, depending on applications) are necessary to configure this system. Typically, an

adequate number of boilers are installed to cover the space-heating load on the design day,

however one or more units are used for the domestic hot water load.
The theory behind this type of system is that the maximum space-heating load and the

maximum domestic hot water load do not occur simultaneously. Therefore, boilers used for

the domestic hot water are capable of switching between constant setpoint and BMS

modes of operation. These boilers are the combination units and are referred to as the

combo boilers. The combo boilers heat water to a constant setpoint temperature. That

water is then circulated through a heat exchanger in a domestic hot water storage tank.
When the space-heating load is such that all the space-heating boilers are at the 100%

valve position, the BMS/ACS will then operate the domestic boilers to become space-

heating boilers, provided the domestic hot water load is satisfied. If the domestic hot water

load is not satisfied, the combo boiler(s) remain on the domestic hot water load. If the

combo boilers switch over to space heating, but there is a call for domestic hot water, the

combo units will resume heating water for domestic needs.
When the combo units are satisfying the domestic load they are in constant setpoint mode

of operation. When the combo units switch over to space heating, their mode of operation

changes to the BMS mode. For more information concerning the operation of the

Combination Control Panel see the AERCO CCP-1 literature (BMS 168 applications) and

Advertising