CHAPTER 7: MAINTENANCE

PR2: 05/09/12 Page

81 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

9. Connect the staged ignition assembly to the gas injector tube of the igniter-injector by

securing the compression nut to the elbow of the staged ignition assembly.

10. Reconnect the igniter-injector cable.
11. Reinstall the side and top panels on the unit.

7.3 FLAME DETECTOR

The flame detector (part no. 66006) is located on the burner plate at the top of the unit (see

Figures 7-1 and 7-2). The flame detector may be hot. Allow the unit to cool sufficiently before

removing the flame detector.
To inspect or replace the flame detector:

1. Set the

ON/OFF switch on the control panel, to the OFF position. Disconnect AC power

from the unit.

2. Remove the side and top panels from the unit.
3. Disconnect the flame detector lead wire.
4. Remove the two (2) screws securing the flame detector to the plate (Figure 7-2 on

previous page). The flame detector is secured to the burner plate with one (1) #10-32

screw and one (1) #8-32 screw.

5. Remove the flame detector and gasket from the burner plate.
6. Thoroughly inspect the flame detector. If eroded, the detector should be replaced.

Otherwise clean the detector with a fine emery cloth.

7. Reinstall the flame detector and flame detector gasket.
8. Reconnect the flame detector lead wire.
9. Reinstall the side and top panels on the unit.

7.4 COMBUSTION CALIBRATION & RSI REGULATOR ADJUSTMENT

The Combustion Calibration settings and RSI Regulator adjustment must be checked at the

intervals shown in Table 7-1 as part of the maintenance requirements. Refer to Chapter 4 for

combustion calibration instructions. Refer to paragraph 7.4.1, below, for RSI regulator test and

calibration instructions.

RSI Regulator Pressure

7.4.1

The BMK1.5LN unit has a RSI (Regulated Staged Ignition) system in the gas train that should

be pressure tested annually. If the pressure is above 5.0” w.c. or below 3.0” w.c., then the RSI

pressure regulator must be recalibrated per paragraph 7.4.1.2.

RSI Regulator Pressure Test

7.4.1.1

The RSI regulator test is performed as follows:

1. Ensure that gas supply shut-off valve upstream of the unit is still turned OFF.
2. Turn OFF electrical power to the system.
3. CLOSE the following valves in the unit’s gas train (refer to Figure 7-4):

RSI Gas Supply Valve

RSI Bleed-off Valve

Manual Shut-off Valve (between the Air/Fuel Valve and the SSOV).