CHAPTER 7: MAINTENANCE

PR2: 05/09/12 Page

85 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

3. Disconnect the lead wire from the flame detector installed on the burner plate. See Figure

7-4.

BLOWER

PROOF

SWITCH

BURNER

PLATE

BLOWER

IGNITER-

INJECTOR

HOSE

CLAMP

FLAME

DETECTOR

STAGED

IGNITION

ASSEMBLY

3/8-16

HEX NUTS

(8)

1/2" BOLTS

& NUTS (4)

AIR/FUEL

VALVE

BLOCKED

INLET

SWITCH

10-32 x 1 /2" LG

GROUNDING

SCREW

Figure 7-4: Burner Assembly Mounting Details

4. Remove the two (2) screws securing the flame detector to the plate. The flame detector is

secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.

5. Remove the flame detector and gasket from the burner plate.
6. Disconnect the cable from the igniter-injector.
7. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector

tube of the igniter-injector to the elbow of the staged ignition assembly (see Figure 7-2).

Disconnect the staged ignition assembly from the igniter-injector.

8. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end

wrench.

9. Disconnect the unit wiring harness connectors from the air/fuel valve and blower motor.
10. Disconnect the wire leads connected to the blower proof switch and blocked inlet switch

(Figures 7-4 & 7-5).

11. Remove the 10-32 x 1/2" long. grounding screw from the burner plate (Figures 7-4 and 7-

5).

12. Disconnect the gas train from the air/fuel valve by removing the four (4) 1/2” bolts and nuts

(Figure 7-4).

13. Disconnect the flex hose from the air/fuel valve by loosening the hose clamp.
14. Remove the four (4) 5/16-18 hex head screws securing the blower to the burner plate

(Figure 7-5).

15. Remove the blower and air/fuel valve from the burner plate by lifting straight up. Also,

remove the blower gasket.

16. Remove the eight (8) 3/8-16 nuts from the burner flange (Figure 7-4) using a 9/16” wrench.

Advertising