Operating Precautions

/!\ CAUTION

1

)

2

)

3)

4)

5)

6

)

7)

8

)

9)

Do not apply power and attempt to use the inverter until this entire operation

manual has been carefully reviewed.

The input voltage must be within +/-10% of the specified input voltage. Voltages

outside of this permissible tolerance range may cause internal protection

devices to turn on or can cause damage to the unit. Also, the input frequency

should be within

+1-2

Hz of the specified input frequency.

Do not use this inverter with a motor whose rated input is greater than the rated

inverter output.

This inverter is designed to operate NEMA B motors. Consult the factory before

using the inverter for special applications such as an explosion proof motor or

one with a repetitive type piston load.

K

danger

/^

Do not touch any internal part with

power applied to the inverter. First

remove the source power and check that the charge and power LED's are out.

A hazard exists temporarily for electrical shock even if the source power

Is removed.

Do not apply commercial power to the output terminals T1 (U), T2 (V), or T3 (W)

even if the inverter source power is off. Disconnect the inverter from the motor

before applying a test or bypass voltage to the motor.

Do not operate this unit with the cabinet door open.

Use caution when setting output frequency. Overspeeding of the motor can

cause serious damage to the motor and/or the driven load equipment.

Use caution when setting the acceleration and/or deceleration time.

Unnecessarily short acc/dec time can cause undue stress and tripping of the

drive.

10)

Interface problems can occur when this inverter is used in conjunction with

some types of process controllers.

Signal isolation may be required to

prevent controller and/or inverter damage.

Contact Toshiba or the process controller manufacturer for further
information about compatibility and signal isolation.

11)

When operating the inverter in the PWM high carrier frequency mode (those

frequencies above 12 kHz), the

electronic thermal protection

/eve/

function

parameter [:tHr] should be changed from the factory setting of 100% to 90%

(see Setup Parameters ITEM 9 page 7-2). This is to compensate for the 10%

derating factor required at 16 kHz operation. Follow the general procedures for

changing function parameters. Further derating may be required for cable runs

of greater than 100 feet.

Contact Toshiba for more information.

12)

Personnel who have access to the adjustments and operation of this equipment

should be familiar with these drive operating instructions and with the machinery

being driven.

2 - 2