8 terminal connections and functions, Terminal connections and functions -7, Toshiba – Toshiba Q-Flowsaver II User Manual

Page 25

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOSHIBA

5.8 Terminal Connections and Functions

Terminal

name

Terminal functions

Terminal

location

LI, L2, L3

(R,

S, T)

T1, T2, T3

(U, V, W)

Input power terminals. Connect to either a 3-phase 50Hz, 200Vac
power supply or to a 3-phase 60Hz, 200 to 230Vac power supply

for models Q2-2035 to Q2-2330.

Input power terminals. Connect to either a 3-phase 50HZ, 380Vac
power supply or to a 3-phase 60HZ, 400 to 460Vac power supply

for models Q2-4055 to Q2-420K.

Output load terminals. Connect these terminals to a 3-phase
induction motor of the proper voltage.

Bus bar

or

power

terminal

block

A

OH

ov

Input terminal for external fault signal.

This is the return terminal for OH.

Terminal

block

FLA, FLB, FLC

P24

RCH(UL)

LOW(LL)

FM

AM

PP

RR

IV

CC

(one of three)

Output terminals of form C contact changes state when a protective
function has been activated (250Vac - 2A).

Output terminal for unregulated 24Vdc power supply
(100mA maximum output current).

Output terminal (open collector). Provides an output signal ground
(50 mAdc max) when the upper limit frequency is reached, when an
acc/dec is complete, or when the output frequency is within a specified

range. The choice is determined by settings of the Output Terminal
Selection function (:0.tb).

Output terminal (open collector). Provides an output signal ground
(50 mAdc max) when a preset low speed or a preset lower limit is

reached. The choice is determined by settings of the Output Terminal
Selection function (:0.tb).

Output terminal for an external analog frequency meter.

Use either an ammeter rated at 1 mAdc at full scale or a voltmeter
rated at 7.5Vdc at full scale.

Output terminal for an external analog ammeter.

Use either an ammeter rated at 1 mAdc at full scale or a voltmeter
rated at 7.5Vdc at full scale.

Control

PWB

terminal

block

Regulated 10Vdc power supply to be used with terminal RR for
remote terminal input.

Analog input terminal for a 0 - 5Vdc (JP2 @ 5V) or 0 -10Vdc

(JP2 @ 10V) external reference signal. Also used for wiring a Ik - 10k
ohm (3k ohm recommended) potentiometer to allow for remote speed
control operation.

Analog input terminal for a 0 - 5Vdc (JP1

(JP1 @ I) external reference signal.

V) or 4 (0) - 20mAdc

This is the common return for PP,RR, and IV terminals.

Do not connect to GND(E).

5 - 7

Advertising