Caution, Toshiba – Toshiba Q-Flowsaver II User Manual

Page 56

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOSHIBA

10.5

Jog

The jogging frequency is immediately output when the remote JOG is activated. The

functions [JOG] and [J.StP] must be preset. In addition, the JOG(SS2) terminal must

be set for "JOG". This is accomplished by setting the function parameter [:l.tb] to 1 or 3.

The terminal connections are shown below:

Terminal Connections Required For Remote Jog

>-

o

z

UJ

O Hz

Terminal

inputs

Notes:

1)

A jogging run cannot be engaged by closing the JOG switch during a run.

2)

The inverter will decelerate at the selected rate during: deceleration stop, coast to stop, and DC

injection stop.

3)

F-CC must be broken for DC injection to be applied; breaking only JOG(SS2)-CC allows the

inverter to accept other input signals and is not a "true" off.

4)

See table on next page for terminal inputs and actions.

10.6

Resetting After a Trip

Pressing reset on the keypad resets the inverter faults. Momentarily closing a normally

open dry contact between terminals RST and COM resets the inverter faults remotely.

When the inverter trips due to an emergency stop or the activation of

one or more of its protective functions, the cause of the fauit must be

CAUTION

corrected before resetting the inverter. A forced restart with out prior

fauit correction measures couid damage the inverter and connected
devices.

1 0 - 3

Advertising