9.3

COMMUNICATION GROUP PARAMETERS (cont'd)

POWER FAILURE FUNCTION SELECTION (ITEM 3) - When this function is selected,

the inverter will use the regenerative energy of a running motor to extend the power off

ride through capability during momentary power dropouts (approximately 100mS). There

are some cases when continuous operation is not possible due to the machines's inertia

or load status, so this feature should be used in combination with the retry function.

This function is valid oniy on the 230 voit units.

FAULT TRIP DATA RETENTION SELECTION (ITEM 4) - This function can be set to

store trip data in the EEPROM. The trip status data stored in this manner is available for

observation while occurring or anytime after the drive has tripped. If the trip data is stored

in this manner then the drive can only be started by manually resetting the drive [:typ]=3.

See Tripped Status Monitoring Page 8-3.

INPUT TERMINAL SELECTION (ITEM 5) - Use this parameter to configure the inverter

to recognize functional combinations of terminal inputs SS2, SS3, JOG, and AD2. See

Input Terminal Operation Chart on page 10-1. This chart shows all of the combinations

and the way that operating frequency can be selected by shorts or opens across these

terminal inputs.

OUTPUT TERMINAL SELECTION (ITEM 6) - Use this parameter to configure the

inverter for output functional combinations of terminals LL, UL, LOW, and RCH. See

Output Terminal Operation Chart on page 10-1. This chart shows output configurations

that can be assigned to these terminals.

OPTION CARD MULTI-FUNCTIONAL SELECTIONS (ITEM 7) - Use this function to

select various configurations for the optional "Multi-function Printed Circuit Board".

This is used oniy when the "Multi-Functionai Option Board" is instalied.

INVERTER NUMBER (ITEM 8) - Use this function to select a number between 0 and 31

to assign the inverter. This will electronically "tag" the inverter when operating on a serial

bus with other inverters.

This is used oniy when the "Muiti-Functional Option Board"

is instalied.

BAUD RATE (ITEM 9) - Use this function to select the serial communication bit transfer

rate.

This is used only when the "Multi-Functional Option Board" is installed.

COMMUNICATION DATA BITS (ITEM 10) - Use this function to select the serial

communication bit word length in the communication protocol.

This is used only when

the "Multi-Functional Option Board" is installed.

COMMUNICATION PARITY CHECK AND STOP BIT (ITEM 11) - Use this function to

select the serial communication protocol.

This is used only when the "Multi-

Functional Option Board" is installed.

PWM CARRIER FREQUENCY (ITEM 12) - Use this function to select the pulse width

modulated carrier frequency. The acoustic noise of the motor changes when the PWM

carrier frequency is changed. Changing the carrier frequency is usually effective in

quieting the mechanical vibration noise caused when a resonance occurs at the load

machine fan cover. Other system characteristics are also affected by the carrier

frequency. Higher carrier frequencies cause additional heating of the inverter because of

faster transistor switching speeds.

Overheating of the inverter may become a

problem at higher carrier frequencies and extremely heavy loads.

Consult factory

before changing.