9.7 PATTERN FREQUENCY GROUP PARAMETERS (cont'd)

RUN FREQUENCY HYSTERESIS (ITEM 24) - Use this function to offset the inverter

run frequency. When the frequency reference signal reaches the Frun + Fhys point,

the drive will ramp the motor to that speed. The inverter will continue to follow the

reference signal until it falls below the Frun - Fhys at which time the drive will ramp

the motor to a stop. See the illustration below.