11.4 Calibration of Remote Meters (cont'd)

Use the following diagram for connecting a Frequency Meter (AM):

Terminal Connection (AM)

AM

Ammeter

CC

Zero adjust

screw

Note: Use a 1 mAdc ammeter or

7.5Vdc voltmeter. Connect the meter

across terminals AM-CC. Use shielded

cable (1000 ft. maximun length).

Use the following procedure to calibrate the (AM) meter:

1

)

2

)

3)

4)

5)

6

)

7)

Start the inverter to output a run frequency such as 60 Hz /-,/ /

j j

Press "down" key while pressing

CLEAR/RESET

to display ;

j— j j

Press either the "up" or "down" key to display

: i—i i i

I I I I

Press the

RUN

key to display :/ [value]

Adjust the analog meter reading to match the digital display reading by pressing

the "up" or "down" keys.

Press the

READ/WRITE

key to store this setting to non-volatile EEPROM

memory.

Press the

CLEAR/RESET

key to return to the normal frequency display

j j j

1 1 - 4