T O S H I B A

2.2

Operating Precautions (cont'd)

/!\ CAUTION

13)

Do not open and then re-close a secondary magnetic contactor (MC) between

the inverter and the load until the Inverter has been turned OFF (output frequency

has dropped to zero) and the motor has stopped rotating.

Abrupt re-application

of the load while inverter is ON or motor is rotating can cause inverter

damage.

14)

The operator of the drive equipment should be properly trained In the operation

of the equipment.

15)

Follow all warnings and precautions; do not exceed equipment ratings.

2.3

Confirmation of Wiring

/!\ CAUTION

Make the following final checks before applying power to the unit:

1

)

2

)

3)

4)

Confirm that source power is connected to terminals LI, L2, L3 (R, S, T).

Connection of incoming source power to any other terminals will damage

the inverter.

The 3-phase source power should be within the correct voltage and frequency

tolerances.

The motor leads must be connected to terminals T1, T2, T3 (U, V, W).

Make sure there are no short circuits or inadvertent grounds and tighten any

loose connector terminal screws.

2.4 Start-Up and Test

/!\ CAUTION

Prior to releasing an electrical drive system for regular operation after installation,

the system should be given a start-up test by competent personnel.

This assures

correct operation of the equipment for reasons of reliable and safe performance. It is

important to make arrangements for such a check and that time is allowed for It.

When power Is applied for the first time the inverter will come up in the factory settings

(See section 7.2). If these settings are incorrect for the application trial run then the

correct settings should be programmed from the control panel before activating the run

button.

The inverter can be operated with no motor connected.

Operation with no

motor connected or use with a small trial motor Is recommended for initial adjustment or

for learning to adjust and operate the inverter.

2.5 Maintenance

A CAUTION

1

)

2

)

3)

Periodically check the operating inverter for cleanliness.

Keep the heatsink free of dust and debris.

A

Periodically check electrical connections for tightness

power is off and locked out).

(make sure

2 - 3