Calibration of Remote Meters

Many times an application requires that a frequency meter (FM) or ammeter (AM) be

remotely located. Attachment and calibration of a remote meter is a easy procedure.

The meter leads should be connected to the appropriate terminals while observing

correct polarity. The calibration of the meter is performed with the inverter keypad while

observing the meter. The meter should be zeroed with the set screw before calibrating.

If the meter is not visible from the inverter site, then the meter should be viewed

periodically as the keypad is adjusted. Also the meter can be connected through a

temporary length of cable for easy viewing. This temporary cable should be the same

size and length as the permanent cable.

Use the following diagram for connecting a Frequency Meter (FM):

Terminal Connection (FM)

FM

CC

Frequency

Meter

Zero adjust

screw

Note: Use a 1 mAdc ammeter or

7.5Vdc voltmeter. Connect the meter

across terminals FM-CC. Use shielded

cable (1000 ft. maximum length).

Use the following procedure to calibrate the (FM) meter:

1

)

2

)

3)

4)

Start the inverter to output a run frequency such as 60 Hz

j j j

Press "down" key while pressing

CLEAR/RESET

key to display ; /—

j j

Press the

RUN

key to display :

q

IJ jj

Adjust the analog meter reading to match the digital display reading by pressing

the "up" or "down" keys.

5)

Press the

READ/WRITE

key to store this setting to non-volatile EEPROM

memory.

6)

Press the

CLEAR/RESET

key to return to the normal frequency display

¡-¡j j j j

Although the above procedure shows calibration of the remote meter at a running

frequency of 60Hz; better resolution of the meter can be obtained if the inverter is

running at the maximum frequency.

The motor load should be disconnected for

FM calibration at the highest frequency.